SC800 T3 Operation
Alarm Configuration Procedures
1. At the Alarm Threshold configuration screen, set the interval for a reporting alarm by typing
the number associated with the alarm (1 - 6) and then press Enter. A highlight appears in
the selected field.
2. Use the arrow keys to toggle through the potential intervals (Report All, 1 Hour,
1 Minute, 1 Second, Infinite) then press Enter when the field displays the desired
setting.
Note
When an alarm is configured with an interval of
threshold value is reached, regardless of how long that takes.
3. To set the threshold for an alarm, type the number of the associated Threshold field (7 - 12)
and then press Enter. A cursor appears in the selected field.
4. Use the arrow keys to toggle through the potential settings: >10, >10,000, >1,000,
>100. Press Enter when the field displays the desired setting.
5. Repeat steps 1-4 for any alarms which have been configured for reporting.
6. After all required changes have been made, type S to Save & Update Unit and then press
Enter. The new alarm intervals and thresholds will go into effect in the DSU immediately.
If you decide not to put your interval/threshold changes into effect, type 0 and then press
Enter to discard these changes and return to Main Menu.
Type 0 and then press Enter to return to the Alarm Configuration menu.
3-12
Report All
SpectraComm 800 T3 Data Service Unit
Installation and Operation Manual
SC800 T3 Configuration Menu
, the alarm will be reported when the
076R160-000
Issue 4