5.3

Preparing for maintenance work

Make sure that the inlet to the lifting station is not used during maintenance.
Make sure that the lifting station cannot be switched on accidentally during maintenance work. This applies in
particular if the control unit is in a different room to the system tank.
5.4

Maintenance jobs

5.4.1

Replace battery

Perform the work described in 5.1
Open the housing cover of the control unit and replace the battery
Screw down the control unit's housing cover, make a potential-free connection if necessary and perform a functional
check (see 3.9.2)
Change the battery once a year
5.4.2

Cleaning the lifting station

Lower the wastewater level in the system tank to a minimum. To do so,
run the wastewater pump in manual operation (see Chapter 4.6) until
the pump draws in air.
Bring the ventilation device <25A> on the backwater preventer <25>
into a horizontal position (as shown), the dammed up wastewater can
flow back from the pressure pipe into the system tank