7. CIM 500 Modbus TCP setup

CAUTION
Electric shock
Minor or moderate personal injury
- Connect CIM 500 only to SELV or SELV-E circuits.

7.1 Connecting the ethernet cable

Use RJ45 plugs and ethernet cable. Connect the cable shield to
protective earth at both ends.
It is important to connect cable shield to earth
through earth clamp or to connect cable shield to
earth in the connector.
Maximum cable length
Speed
Cable type
[Mbits/s]
10
CAT5
100
CAT5e, CAT6
CIM 500 is designed for flexible network installation; the built-in
two port switch makes it possible to daisy chain from product to
product without the need of additional ethernet switches. The last
product in the chain is only connected to one of the ethernet
ports. Each ethernet port has its own MAC address.
Ethernet
switch
CIM
500
CIM
500
Fig. 14 Example of Industrial Ethernet network
2
1
6
4
5
Fig. 15 Example of ethernet connection
Maximum cable length
[m/ft]
100 m / 328 ft
100 m / 328 ft
CIM
CIM
500
500
3
7
8
9
Pos.
Description
1
Industrial Ethernet RJ45 connector 1
2
Industrial Ethernet RJ45 connector 2
3
Rotary switch for protocol selection
4
Data activity LED for connector 1
5
Link LED for connector 1
6
Data activity LED for connector 2
7
Link LED for connector 2
Green and red status LED for ethernet
8
communication
Green and red status LED for internal
9
communication between the module and
the CIU 502 unit.

7.2 Setting the Industrial Ethernet protocol

The CIM 500 ethernet module has a rotary switch for selection of
the Industrial Ethernet protocol. See fig. 16.
Fig. 16 Selecting the Industrial Ethernet protocol
Pos.
Description
0
PROFINET IO (default from factory)
1
Modbus TCP
2
BACnet IP
3
EtherNet/IP
4
GRM IP
Reserved, LED1 will be permanently red to indicate an
5..E
invalid configuration
Reset to factory default.
Note that the rotary switch has to be set in this position
F
for 20 seconds to Reset to factory default. During this
period, LED1 flashes red and green at the same time to
indicate that a reset will occur.
Every change of the rotary switch setting, when the
module is powered on, will cause the module to
restart.
Designation
ETH1
ETH2
SW1
DATA1
LINK1
DATA2
LINK2
LED 1
LED 2
13

Advertisement