9.8 Pump 1 register block

All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name
00401
Pump1.MotorTemperature
00402
Pump1.ElectronicTemperature
00403
Pump1.AverageLineVoltage
00404
Pump1.AverageLineCurrent
00405
Pump1.AverageLineCurrentLatest
00406
Pump1.LineFrequency
00407
Pump1.PhaseSequence
00408
Pump1.CosPhi
00409
Pump1.Power
00410
Pump1.EnergyTripCounterHI
00411
Pump1.EnergyTripCounterLO
00412
Pump1.WaterLevel
00413
Pump1.WaterLevelMax
00414
Pump1.MaxContinousTime
00415
Pump1.TotalPoweredTimeHI
00416
Pump1.TotalPoweredTimeLO
00417
Pump1.OperationTimeHI
00418
Pump1.OperationTimeLO
00419
Pump1.OperationTimeTripCounterHI
00420
Pump1.OperationTimeTripCounterLO
00421
Pump1.NumberOfStartsHI
00422
Pump1.NumberOfStartsLO
00423
Pump1.NumberOfStartsTripCounterHI
00424
Pump1.NumberOfStartsTripCounterLO
00425
Pump1.AlarmCode
00426
Pump1.WarningCode
00427
Pump1.OperatingMode
Bit 0: Subpump1AlarmsPhaseSequence
Bit 1: Subpump1AlarmsOvervoltage
Bit 2: Subpump1AlarmsUndervoltage
Bit 3: Subpump1AlarmsOverload
Bit 4: Subpump1AlarmsBlockedMotor
Bit 5: Subpump1AlarmsAlarmBit5
Bit 6: Subpump1AlarmsMotorTemperature
00428
Bit 7: Subpump1AlarmsElectronicTemperature
Bit 8: Subpump1AlarmsTermoRelay1
Bit 9: Subpump1AlarmsTermoRelay2
Bit 10: Subpump1AlarmsVerificationError
Bit 11: Subpump1AlarmsAlarmBit11
Bit 12: Subpump1AlarmsSensorFault
Bit 13: Subpump1AlarmsAlarmBit13
28
Scale
Description
0.01 K
Motor temperature, pump 1.
0.01 K
Electronics temperature, pump 1.
0.1 V
Average supply voltage, pump 1.
0.1 A
Average supply current, pump 1.
Average supply current the last time pump 1 was
0.1 A
operating.
0.1 Hz
Frequency of power supply, pump 1.
Bool
Phase sequence of power supply, pump 1.
0.01
Power factor, pump 1.
1 W
Power consumption, pump 1.
Energy consumption, pump 1.
1 kWh
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
0.01 m
Water level as estimated by pump 1.
Logged maximum value of water level, pump 1.
0.01 m
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
Logged maximum value of continuous operating time
within the last 30 days, pump 1.
1 minute
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
Total time that pump 1 has been powered on.
1 minute
Used as time stamp for alarms in the alarm log the
moment the alarm appears.
1 minute
Total time that pump 1 has been operating.
Trip counter of the total time that pump 1 has been
operating.
1 minute
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
Unscaled
Total number of starts, pump 1.
Unscaled
Trip counter of total number of starts, pump 1.
Grundfos-specific alarm code, pump 1.
Unscaled
See section
14.2 CIU
Grundfos-specific warning code, pump 1.
Unscaled
See section
14.2 CIU
Operating mode of pump 1.
0: "Auto" mode (power-on default)
Bits
1: Forced start
2: Forced stop.
Phase sequence reversed
Overvoltage
Undervoltage
Overload
Blocked motor/pump
-
Motor temperature
Temperature, control electronics
Temperature relay 1 in motor, for example Klixon
Temperature relay 2 in motor, for example thermistor
Verification error, code area (ROM, FLASH)
-
Sensor fault
-
262.
262.