TableA.1 General specifications
Operating ambient temperature
Storage temperature
Operating ambient relative humidity
Dust
Degree of contamination
Corrosive gas
Operating altitude
Vibration resistance
Shock resistance
Insulation resistance
Dielectric strength
EMC zone
Grounding
Installation location
Cooling method
Weight
External dimensions
Target durable years
120
6F8C1497
The specifications of base unit BUM7B dedicated to the migration system are shown
below.
The general specifications of type1 light apply to those of BUM7B.
Item
0° - 55°C (24-hour average temperature: 40°C or less)
-40° - +70°C
10 - 95%RH, level RH2 (no condensation)
0.3mg/m
2 (normal state, no conductive contamination) or less
No corrosive gas
No silicon-containing substance
Up to 2000m above the sea level
IEC60068-2-6, test Fc-compliant
10 cycles in each of the X, Y, Z directions
IEC60068-2-27, test Ea-compliant 147m/s
Three times in each of three orthogonal axis directions)
500Vdc Megger, 10 Mohm or more (power terminal - FG)
2000Vac, one minute (power terminal - FG)
Zone B (including zone A)
D class grounding
Inside of the indoor control panel
Natural cooling
Approx. 11 kg (with all slots used and the conversion adapter installed)
Approx. 5 kg (without load and accessories)
480 mm(W) x 250 mm(H) x 167.5mm(D)
10 years (operating ambient temperature: 40°C)
*1: The reference temperature measurement position is 50mm below the bottom of the base unit.
*2: For long-term storage, store spare parts in dark places and avoid hot or wet places.
For long-term storage, the temperature and humidity should be 0° - 40°C and 20-80 %RH (no
condensation) respectively, and the temperature variation rate should be 10°C/h or less.
Particularly, high ambient temperatures affect the estimated usable periods of batteries and power
supplies. Store them at room temperature (25°C or less).
*3: The following components shall not be contained:
Hydrogen sulfide, sulfurous acid gas, chlorine gas, nitrogen oxides (NOx), sulfur oxides (SOx), ammonia,
silicon gas, etc.
*4: 5 ≤ f < 8.4Hz: Half amplitude 3.5mm, 8.4 ≤ f < 150Hz: Constant acceleration 9.8m/sec
*5: Grounding other than Class D grounding (e.g., mesh grounding) can be used for the system, provided
that the equivalent effect as with Class D grounding can be achieved. For grounding other than Class D,
the user needs to confirm the effect of the grounding.
*6: The "target durable years" in the general specification indicates the "design life" (target value), which is
not a guaranteed value.
The chance failure period of a product is generally referred to as durable years or service life. A
component which stops functioning before the design life of the product due to secular change or heavy
use is referred to as the limited-life part. Aluminum electrolytic capacitor, relays, fuses and
photo-couplers are classified to these parts in BUM7B.
The whole unit of BUM7B should be replaced, since it contains the limited-life aluminum electrolytic
capacitor at an average operating ambient temperature of 40°C and in standard installation condition
(natural cooling). The recommended replacing interval is 10 years.
In addition, the whole unit of module should be replaced if it contains the aluminum electrolytic capacitor.
The recommended replacing interval is 10 years.
Specification
3
(no conductive dust)
2
2
Remarks
*1
*2
*2
*3
*4
*5
Excluding protrusions
*6