Equipment Grounding Conductors; Grounding Electrode Conductors; System Bonding Jumpers; Table 2-4, Equipment Grounding Conductor Sizing - Magnum Energy MagnaSine Hybrid MSH3012RV Owner's Manual

Pure sine wave inverter/charger
Table of Contents

Advertisement

Installation
2.6.1

Equipment Grounding Conductors

The inverter case and all other noncurrent-carrying exposed metal surfaces in the entire electrical
system—that may be accidentally energized—must be grounded. The equipment-grounding
conductor must be sized to safely carry the maximum ground-fault current likely to be imposed
on it from where a ground-fault may occur. In accordance with the NEC, use Table 2-4 to size
the equipment-grounding conductors according to the rating of the overcurrent device protecting
the circuit.
CAUTION: The connections and wiring for the equipment-grounding conductor must be
continuous to allow fault currents to properly operate overcurrent devices. Whenever
equipment is removed that disconnects the bonding connection between the grounding
electrode conductor and the exposed conducting surfaces, a bonding jumper must be
installed while the equipment is being removed.
AC Side – The AC equipment grounding conductor (EGC–AC) is sized per Table 2-4 and is connected
to the inverter's AC equipment grounding terminal shown in Figure 2-8.
DC Side – Since the currents on the DC side are much higher than the AC side, the equipment
grounding needs are different. The DC equipment grounding conductor (EGC–DC) is sized per
Table 2-4 and connected to the DC equipment grounding terminal on the inverter as shown in
Figure 1-2, Item 8.
Info: The equipment grounding conductors (EGC) and the grounding electrode
conductors (GEC) must be either insulated (green or green with a yellow stripe) or
bare copper. However, for conductors larger than #6 AWG (13.3 mm
insulation can be colored green, or covered with green tape or green adhesive labels.

Table 2-4, Equipment Grounding Conductor Sizing

Rating of
Overcurrent Device
20 amps
30 – 60 amps
100 amps
2.6.2

Grounding Electrode Conductors

AC Side – The size of the AC grounding electrode conductor (GEC–AC) depends on the size of the
largest ungrounded conductor feeding the AC load center. For ungrounded conductors that are #2
AWG (33.6 mm
) or smaller, use a minimum #8 AWG (8.4 mm
2
DC Side – When the DC (GEC-DC) and AC (GEC-AC) grounding electrode conductors are connected
to a single grounding electrode, the size of the DC grounding electrode conductor cannot be smaller
than the largest conductor in the DC system (usually the battery-to-inverter cable).
2.6.3

System Bonding Jumpers

AC Side – The AC system bonding jumper (SBJ) provides the neutral-to-ground "bond" between
the grounded conductor (AC neutral) and the equipment grounding conductor, and is required
in only one place in the AC electrical system. When the MSH3012RV is connected to an external
AC source (i.e., shorepower), the external AC source must provide the bond. However, when the
external AC source is disconnected and the inverter is providing the AC power (i.e., inverting), an
internal relay inside the inverter connects the neutral and ground to provide the bond. See Section
2.6.5 for more information on the neutral-to-ground switching feature.
DC Side – The size of the system bonding jumper (SBJ) in the DC electrical system must not be
smaller than the DC grounding electrode conductor (GEC–DC) used.
Page 27
Minimum Size of
Copper Ground Wire
#12 AWG (3.3 mm
)
2
#10 AWG (5.3 mm
)
2
#8 AWG (8.4 mm
)
2
Rating of
Overcurrent Device
200 amps
300 amps
400 amps
) copper conductor.
2
© 2020 Sensata Technologies
) the exposed
2
Minimum Size of
Copper Ground Wire
#6 AWG (13.3 mm
)
2
#4 AWG (21.1 mm
)
2
#3 AWG (26.7 mm
)
2

Advertisement

Table of Contents
loading

Table of Contents