Installation
Step 3: Connecting the MicroGTs to the PV Modules
Use Figure 6 when connecting the DC cables from the PV modules to
the MicroGT 500 inverters.
Figure 6, Connecting MicroGTs to the PV Modules
Note: Upon connecting the DC cables to the fi rst module, the MicroGT
500 inverter's LED (on bottom of unit) should blink red, followed by
three green blinks—indicating that the MicroGT inverter is functioning
correctly. This test function starts and ends within 5 seconds of
connecting the DC cables, so pay careful attention to the LED when
performing this task. This only occurs when DC voltage is applied to
the fi rst module. The LED will not fl ash when the second module is
connected.
Step 4: Grounding the System
Each MicroGT 500 comes with a ground clamp that can accommodate
a single #6 AWG (13.3 mm
electrical code for grounding conductor sizing requirements.
Note: If you used grounding washers to ground the MicroGT 500's
chassis to the PV racking—per Note in Step 2—skip this step.
1. Connect the grounding electrode conductor to the MicroGT 500
inverters' ground clamps (Figure 7).
Note: The AC output neutral is not bonded to ground inside the
MicroGT 500 inverter.
Figure 7, Grounding the System using the Grounding Clamp
6
DC MC4 Connectors
) copper ground wire. Check your local
2
© 2016 Sensata Technologies