Battery Bank Sizing Worksheet - Magnum Energy MagnaSine Hybrid MSH3012RV Owner's Manual

Pure sine wave inverter/charger
Table of Contents

Advertisement

Appendix B – Battery Information
B-5 Battery Bank Sizing Worksheet
Complete the steps below to determine the battery bank size required to power your AC loads:
1. Determine the daily power needed for each load
a) List all AC loads required to run; and
b) List the Wattage for each load (see Table C-1 for common loads/wattage); and
c) multiply by how many hours per day (or a fraction of an hour) each load will be used; and
d) multiply by how many days per week you will use the listed loads; and
e) divide by seven = Average Daily Watt-Hours Per Load.
AC load
Wattage
2. Determine the total power needed each day for all the loads.
• Add all Average Daily Watt-Hours Per Load = Total Daily Watt-Hours.
3. Determine the battery amp-hour capacity needed
to run all the loads before recharging.
• Divide the Total Daily Watt-Hours by the nominal
battery voltage of the inverter (i.e., 12 volts); and
 Multiply this by # of days the loads will need to run
without having power to recharge the batteries
(3 to 5 days of storage) = Storage Amp-Hours.
4. Determine how deeply you want to discharge your batteries.
• Divide the Storage Amp-Hours by 0.2 or 0.5 to get the Total Amp-Hours:
a) 0.2 = Discharges the batteries by 20% (80% remaining), this is
considered the optimal level for long battery life; or
b) 0.5 = Discharges the batteries by 50% (50% remaining), this is
considered a realistic trade-off between battery cost and battery life.
Additional compensation:
Low battery temperature: If the batteries are installed in a location that will be exposed to low
temperatures, the available output will be less. In these instances, you will need to determine
the lowest temperature the battery bank will experience and multiply the Total Amp-Hours by the
multiplier below.
Temperature
80F/27C
Multiplier
1.00
Inverter effi ciency: When used in a back-up power application the inverter effi ciency will not be a
large concern; however, if the inverter is the primary AC source for the calculated load, the Total
Amp-Hours should be multiplied by 1.2 to factor in an average 80% inverter effi ciency.
Page 53
Average Daily Watt-Hours Per Load
(x) hours per day (x) days per week
70F/21C
60F/15C
1.04
1.11
(inverter battery voltage)
÷ ___ =
(days of storage)
x ___ =
50F/10C
40F/4C
1.19
1.30
© 2020 Sensata Technologies
÷
(
7) = total power
Total Daily
Watt-Hours
Total Amp-Hours
30F/-1C
20F/-7C
1.40
1.59

Advertisement

Table of Contents
loading

Table of Contents