Installation; General Installation Guidelines; Dimensions In Mm - Pilz PNOZ ml1p Operating Manual

Configurable safety systems pnozmulti
Hide thumbs Also See for PNOZ ml1p:
Table of Contents

Advertisement

Installation

5
Installation
5.1

General installation guidelines

The control system should be installed in a control cabinet with a protection type of at
}
least IP54. Fit the control system to a horizontal mounting rail. The venting slots must
face upward and downward. Other mounting positions could destroy the control system.
Use the notches on the rear of the unit to attach it to a mounting rail. Connect the con-
}
trol system to the mounting rail in an upright position, so that the earthing springs on the
control system are pressed on to the mounting rail.
The ambient temperature of the PNOZmulti units in the control cabinet must not exceed
}
the figure stated in the technical details, otherwise air conditioning will be required.
To comply with EMC requirements, the mounting rail must have a low impedance con-
}
nection to the control cabinet housing.
5.2

Dimensions in mm

Operating Manual PNOZ ml1p
21575-EN-06
CAUTION!
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure against discharge
before touching the product, e.g. by touching an earthed, conductive sur-
face or by wearing an earthed armband.
94 (3.70")
22,5
(0.88")
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

773540773545

Table of Contents