NTP- G145 Connect a Multishelf Node and Subtending Shelves to an MS-ISC-100T Card
Figure 1-34
To connect a subtending shelf to the EAP, complete the following (see
Step 2
Using a cross-over (CAT-5) LAN cable, plug one connector into the front panel of the subtending
a.
shelf TCC2/TCC2P card in Slot 7 and plug the other end into the SSC1 port on the left EAP.
Using a cross-over (CAT-5) LAN cable, plug one connector into the front panel of the subtending
b.
shelf TCC2/TCC2P card in Slot 11 and plug the other end into the SSC1 port on the right EAP.
Repeat Steps
c.
port number (2 through 8) on the left and right EAP for each subtending shelf.
Stop. You have completed this procedure.
Cisco ONS 15454 DWDM Procedure Guide, R8.0
1-82
Connecting the EAP to the Node Controller and Subtending Shelf
EAP
Subtended Shelf
RJ-45
RJ-45
TCC2/
TCC2/
TCC2P
TCC2P
Slot 7
Slot 11
Node Controller Shelf
DCN1
DCN2
SSC1
SSC2
SSC3
SSC4
SSC5
SSC6
SSC7
NC
RJ-45
RJ-45
PRT
UA
TCC2/
TCC2/
MS-ISC
TCC2P
TCC2P
Slot 6
Slot 7
Slot 11
a
and
b
for each subtending shelf in the multishelf configuration. Use the same SSC
Chapter 1 Install the Shelf and Common Control Cards
EAP
DCN1
DCN2
SSC1
SSC2
SSC3
SSC4
SSC5
SSC6
SSC7
NC
PRT
UA
MS-ISC
Slot 12
Figure
1-34):