4100ES-S1 Programming Guide
Appendices
12.4
Appendix D - Custom Control for Alarm Zone Facilities
A 4100-1282 8 Pushbutton/8 red LED/8 amber LED module is fitted for each 8 zones to
display the alarm and isolate states of the zones (lists) and allow the zone to be isolated,
alarm tested or fault tested.
This diagram shows the point numbers used for the push buttons and LEDs, where n = zone
number. A number of pseudo digital points are used for each zone to store and control the
operation.
3-65 Zone 1 Multifunction Button (P901)
x-x Zone n Multifunction Button (P900+n)
12.4.1 Digital Points used
Zone 1
P601
P701
P801
P901
P1001
P1101
Zone n
P600+n
P700+n
P800+n
P900+n
P1000+n
P1100+n
– Zone 1 is Isolated
– Zone 1 Isolate Toggle
– Zone 1 is in Alarm
– Zone 1 Multifunction pushbutton
– Zone 1 is in Alarm Test
– Zone 1 is in Fault Test
– Zone n is Isolated
– Zone n Isolate Toggle
– Zone n is in Alarm
– Zone n Multifunction pushbutton
– Zone n is in Alarm Test
– Zone n is in Fault Test
12-16
3-1 Zone 1 Alarm LED
3-2 Zone 1 Isolate LED (P601)
x-x Zone n Alarm LED
x-x Zone n Isolate LED (P600+n)
Document: LT0400