Document: LT0400
3-3 ASE Fault Relay
[INPUTS]
STATUS ON
A2 | ANALOG | ANALOG | NUMBER OF SYSTEM TROUBLES
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=7,7
0-7-4 | MCODE7 | RELAY | Master Output - City Trouble Relay
TRACK ON PRI=7,7
1-12 | SPECOUT | SPECOUT | CITY TBL/OPT RELAY 3
[END OUTPUTS]