Addressable Device Settings
6.1

Introduction

6.1.1

Alarm Device Types

The 4100ES-S1 supports a range of addressable device types on its IDNet addressable
loops. The following sections detail for each of the compatible addressable devices
(detectors and modules) what device type and what point type should be selected in the ES
Programmer. Other point types should not be used without consulting a TFPP/Simplex
technical representative as most have code associated with them that can activate outputs
automatically with no isolate control. The device type defines what type of device it is,
including, for detectors, what type of base is used. The point type defines how the device is
to be used, i.e., the functionality or application.
6.2

Addressable Detector Settings

6.2.1

4098-9714E Photo Detector

Device Types
PHOTO
IPHOTO
SPHOTO
Point Types
SMOKE
VSMOKE
DUCT
UTILITY
6.2.2

4098-9717E Ion Detector

Device Types
ION
IION
SION
Point Types
SMOKE
VSMOKE
6.2.3

4098-9733E Heat Detector

Device Types
HEAT
IHEAT
SHEAT
OHEAT
IOHEAT
SOHEAT
UHEAT
Point Types
HEAT
UTILITY
– Standard photo detector on Standard base
– Standard photo detector on Isolator base
– Standard photo detector on Sounder base
– Standard setting
– Verified Smoke Detector (Recommended setting to reduce nuisance
alarms)
– Return Air Duct detector
– Supply Air or Stair Pressurization Duct detector
– Standard ion detector on standard base
– Standard ion detector on Isolator base
– Standard ion detector on Sounder base
– Standard setting
– Verified Smoke Detector (Recommended setting to reduce nuisance
alarms)
– Standard heat detector on standard base
– Standard heat detector on Isolator base
– Standard heat detector on Sounder base
– Standard heat detector with Rate of Rise on standard base
– Standard heat detector with Rate of Rise on Isolator base
– Standard heat detector with Rate of Rise on Sounder base
– Heat detector that can only be used as a Utility (non-MAF) detector
– Standard setting
– Heat detector used for non-MAF usage only