Document: LT0400
6.2.4

4098-9754E Multi-Sensor Photo Heat Detector (COMBO)

Mx-x-0 Parent Point
Device Type
COMBO
ICOMBO
SCOMBO
st
Mx-x-1 1
Sub Point
Device Type
MPHOTO
Point Type – Photo Part
SMOKE
VSMOKE
DUCT
nd
Mx-x-2 2
Sub Point
Device Type
MHEAT
Point Type – Heat Part
MHEAT
MOHEAT
rd
Mx-x-3 3
Sub Point
Device Type
MARCOR
MAOFF
Point Type – R-Correlation Part
UTILITY
6.3

Addressable Device Settings

Any unused points should be set as utility to avoid potential false alarms from unused fire
point type inputs.
6.3.1

4099-9032 MCP

Device Type
KACPULL – Standard MCP
Point Type
PULL
6.3.2
4090-9001/4090-9051 Supervised Input IAM
The 4090-9051 is an encapsulated version of the 4090-9001, with wire leads instead of
terminals. Programming and performance are identical.
Device Type
IAM
Point Type
FIRE
UTILITY
TROUBLE – Input used to indicate a Fault status
– Standard Multi-Sensor detector on standard base
– Standard Multi-Sensor detector on Isolator base
– Standard Multi-Sensor detector on Sounder base
– Standard setting
– Standard setting
– Verified Smoke Detector (Recommended setting to reduce nuisance
alarms)
– Duct detector
– Standard setting
– Standard setting
– Standard heat detector with Rate of Rise
WARNING: DO NOT USE THIS SETTING SINCE THIS IS NOT
APPROVED IN AUSTRALIA – USE MAOFF INSTEAD
– Choose this setting for Australian use.
– Standard setting for MAOFF
– Standard setting
– Standard setting
– General Fire Point.
– Input used by Custom Control Logic only
6-3
4100ES-S1 Programming Guide