Appendix D - Custom Control For Alarm Zone Facilities; Digital Points Used - Simplex 4100-S1 Programming Manual

Fire indication panel
Table of Contents

Advertisement

4100U-S1 Programming Guide
Appendices

12.4 Appendix D - Custom Control for Alarm Zone Facilities

A 4100-1282 8 Pushbutton/8 red LED/8 amber LED module is fitted for each 8 zones to
display the alarm and isolate states of the zones (lists) and allow the zone to be isolated,
alarm tested or fault tested.
This diagram shows the point numbers used for the push buttons and LEDs, where n = zone
number. A number of pseudo digital points are used for each zone to store and control the
operation.
3-65 Zone 1 Multifunction Button (P901)
x-x Zone n Multifunction Button (P900+n)

12.4.1 Digital Points used

Zone 1
P601
P701
P801
P901
P1001
P1101
Zone n
P600+n
P700+n
P800+n
P900+n
P1000+n
P1100+n
Page 12-16
– Zone 1 is Isolated
– Zone 1 Isolate Toggle
– Zone 1 is in Alarm
– Zone 1 Multifunction pushbutton
– Zone 1 is in Alarm Test
– Zone 1 is in Fault Test
– Zone n is Isolated
– Zone n Isolate Toggle
– Zone n is in Alarm
– Zone n Multifunction pushbutton
– Zone n is in Alarm Test
– Zone n is in Fault Test
15 December 2010
3-1 Zone 1 Alarm LED
3-2 Zone 1 Isolate LED (P601)
x-x Zone n Alarm LED
x-x Zone n Isolate LED (P600+n)
Document: LT0400
Issue 1.4