SIEB & MEYER SD2 Hardware Description page 172

Drive system
Hide thumbs Also See for SD2:
Table of Contents

Advertisement

Appendix D: Manufacturers
20.D
172
The maximum current (I
device.
You can order the suitable SIEB & MEYER line filter for your device by its individual
article number:
SIEB & MEYER article
Rated voltage (U
number
0110073E
400 V
0110080
400 V
EPCOS Line Filters
1- and 3-phase line filters
high attenuation
partial RCD compatibility
The maximum current (I
device.
When such a line filter is used, very high leakage currents arise, because
Cy > 1.5 μF. For this reason it is only partially compatible with an RCD
(residual current protective device).
You can order the suitable EPCOS line filter for your device at SIEB & MEYER by its
individual article number:
SIEB & MEYER article
EPCOS article number Rated voltage (U
number
35063105
B84143A0016R105
35063103
B84143A0050R105
35063106
B84143A0090R105
) must be adapted to the back-up fuses of the
max
)
Rated current (I
)
rated
rated
17 A
36 A
) must be adapted to the back-up fuses of the
max
)
rated
520 / 300 V
520 / 300 V
520 / 300 V
Drive System SD2 - Hardware Description
W
Leakage current (I
)
leak
≤ 3.5 mA
≤ 3.5 mA
Rated current
Leakage
(I
)
current (I
)
rated
leak
16 A
15 mA
50 A
15 mA
90 A
18 mA

Hide quick links: