Chapter 6
•
32 – Wet Mix
•
64 – Mix Complete
•
128 – Paused
It is also possible to get combinations of status (such as pause and wet mix) in this case 32+128
= 160 would be returned
Mixer Control Commands
3.6
To issue start, pause, resume and reset commands to the unit the following command can be
used
•
>C1=nn
Where nn is equal to the command sent
•
01 – start
•
02 – pause
•
03 – resume
•
04 – reset
•
05 – cement in
IO Status
3.7
It is also possible to retrieve the current status of the Onboard IO. The following command can
be used to do this
•
>S1=n
n can b e 0, 1 or 2. If n = 0 then a status word will be sent where:
•
1 – Cement In
•
2 – Start/Resume
•
4 – Pause/Reset
•
8 – Water Meter
•
16 – Water Tank full
•
32 – Coarse Valve
•
64 – Fine Valve
•
128 – Pre-wet done signal
•
256 – Mix complete signal
•
512 – Alarm signal
•
1024 – Request Admix
•
2048 – Unassigned Output
If nn = 1 then a status byte will be sent for the Expansion Board inputs
•
0 – No Daughterboard
•
1 – Digital input 1
•
2 – Digital input 2
•
4 – Digital input 3
•
8 – Digital input 4
•
16 – Digital input 5
•
32 – Digital input 6
•
64 – Digital input 7
•
128 – Digital input 8
Hydro-Control VI Installation Guide HD0455 Rev 1.9.0
RS232 Interface
83