Rev A
Released 10/3/2013
Page 2 of 10

6.3 Power Requirements

The control cabinet can accept power from multiple power sources. Each power input source (30 A / 120 V ac, 15 A / 240 V
ac, or 30 A / 125 V dc) should feed through its own external, two-pole, thermal, magnetic circuit breaker before entering the
control system enclosure. The breaker should be supplied in accordance with required site codes. The circuit breaker must be
included in the installation. If used as the panel disconnect, it must be suitably located and easily reachable. The circuit
breaker must be marked as the disconnecting device and suitably located near the equipment for servicing.
Mark VIe control systems may use up to three mains supplies; two for redundant control power (ac and / or dc) and one
auxiliary ac supply for accessories such as cabinet lights and fans. The following are example mains power supply rating
labels used on the front cabinet door where the panel main power is to be connected.
(75 [2.95])
Referencing the designators from the rating label, AC1 and optional AC2 may be 120 V ac or 240 V ac, 50/60 Hz. DC1 and
optional DC2 are 220 V dc supplies that may be used instead of AC1 and AC2. DC is an optional floating source 125 V dc
supply, usually a battery. AUXAC is used only to supply internal auxiliary appliances, such as fans, heaters, lights, or socket
outlets. The AC1, AC2, DC, DC1, or DC2 mains supplies may feed one or more Switch Mode Power Supplies to provide 28
V dc control power, or 24 or 48 V dc wetting for contact I/O circuits.
AC1 and AC2 may also feed one or two optional DACA Line Rectified Power Supplies. Each DACA is factory-set for either
120 or 240 V ac input, and provides a floating 107 V dc output. The DACA DC output may be connected through an internal
diode with the DC optional 125 V dc supply to provide diode OR'd dc redundancy to feed Switch Mode Power Supplies,
external loads such as solenoids, and /or wetting for contact I/O circuits.
Note To comply with Low Voltage Directive 2014/35/EU, all ac and dc power supply mains must connect through a Mark
GE Energy
VIe Overvoltage Transient Protection and EMI Filter circuit. These OV and EMI filter circuits are built-in to the JPDB and
JPDF Power Distribution Modules. If JPDB/JPDF are not used to distribute ac and dc power supply mains to the Mark VIe
GE PROPRIETARY
INFORMATION
control, then a separate GE Filter Module 246B8279Gx should be used to filter the mains. Refer to Mark VIe and Mark VIeS
Control Systems Volume II: System Guide for General-purpose Applications (GEH-6721 Volume II), the chapter PDM Power
SIZE
CAGE CODE
A
Distribution Modules.
NONE
SCALE
132
GEH-6721_Vol_I_BP
DWG Number 109T7428
Rev A
(100 [3.94])
(75 [2.95])
P0002
©COPYRIGHT 2013 GE
ENERGY (USA), LLC AND/OR ITS AFFILIATES.
GE CLASS II (INTERNAL CRITICAL)
All rights reserved. The information contained
herein is GE Energy C & PE COE Proprietary
GENERAL ELECTRIC COMPANY
Technical Information that belongs to the General
Electric Company, GE Energy (USA), LLC and/or
their affiliates, which has been provided solely for
the express reason of restricted private use. All
persons, firms, or corporations who receive such
information shall be deemed by the act of their
receiving the same to have agreed to make no
DATA NAMEPLATE
duplication, or other disclosure, or use whatsoever
for any, or all such information except as expressly
MARK VI LINE
authorized in writing by the General Electric
Company, GE Energy (USA), LLC and/or its
affiliates.
DWG NO.
109T7428
GE Proprietary Information - Class II (Internal) US EAR - NLR
GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I
Released 10/3/2013
Page 6 of 10
(100 [3.94])
GE Energy
SALEM, VA.
GE PROPRIETARY
INFORMATION
SIZE
CAGE CODE
A
REV
A
NONE
SCALE
SHEET 2 of 10
Public Information
P0006
GE CLASS II (INTERNAL CRITICAL)
GENERAL ELECTRIC COMPANY
SALEM, VA.
DATA NAMEPLATE
MARK VI LINE
DWG NO.
109T7428
GE Proprietary Information - Class II (Internal) US EAR - NLR
REV
A
SHEET 6 of 10