6.10.2 BPPC-based Mark VIe I/O Packs
Mark VIe I/O packs typically have a part number that ends with 'H1B'. Refer to the section,
available components. There are several guidelines to keep in mind when BPPB-based I/O packs are migrated to BPPC-based
I/O packs.
The minimum firmware for a particular BPPC-based I/O pack is listed in GEH-6721_Vol_II or volume III in that particular
component chapter, subsection, Compatibility. Firmware can be installed from the ControlST DVD onto the HMI without
upgrading the system (with minimum ControlST V04.04).
Installation Guidelines
Mark VIe System at ControlST V04.04 or Later
The ControlST software suite includes Windows
configuration and monitoring tools coupled with firmware
for all Mark VIe controllers and I/O packs. A sample of
tools and components follows.
Note A Mark VIe system requires ControlST V04.04 or
later to introduce a BPPC-based I/O pack. Refer to the
ControlST Software Suite Upgrade Instruction Guide
(GEI-100694) for detailed instructions on the system
upgrade procedure.
Public Information
I/O Types
ToolboxST application
WorkstationST* features
WorkstationST Alarm Viewer
Mark VIe controller firmware
PDIA I/O pack firmware
PDOA I/O pack firmware
GEH-6721_Vol_I_BP System Guide 159