Perform the following troubleshooting steps if needed:
It is not possible to connect to the designated controller if the controllers are set in the dc determination state. Going
online with each individual controllers is required.
The ToolboxST application may not display any information in the Status tab for the faulty Mark VIe control if it is set
in the Power on/d0-MASTER_INITIALIZATION state. The other two controllers are suspended at d1-State Designated
Controller Determination state.
If the controller halts before d0-MASTER_INITIALIZATION (at power on state), the problem could be with the
controller. If the controller halts at d0-MASTER_INITIALIZATION state, the controller may have lost its IP address.
If the controllers halt at the d1-dc_DETERMINATION state, one of the controllers may be unable to communicate to
either IONet 1, 2, or 3 port.
If all the controllers halt at the d3-INPUTS_ENABLED state, at least one of the I/O modules configured as a required
module may not be communicating with the controllers.