8.9.1 Communication Errors
When firmware and application is downloaded to an I/O module, it can take several minutes to install, restart, and re-establish
communication to the Mark VIe controller. If the ATTN LED is red and flashing at 2 Hz 50%, the IP address has not been
received from the controller. For information on ATTN LED flash codes, refer to the Help file for the specific I/O module and
the section Diagnostics.
Verify that the terminal board bar code configured in the ToolboxST configuration matches the actual hardware.
Verify that the terminal board type, including HW Form, in the ToolboxST configuration matches the terminal board in
the actual I/O module.
Verify that the network cables and switches to the I/O module are plugged in correctly, and that the Link and Activity
LEDs are active.
➢ ➢ To view more troubleshooting information: from the Diagnostics tab, select each diagnostic alarm and press F1.