BPPC-based I/O pack
162
GEH-6721_Vol_I_BP
Auto-Reconfiguration for BPPB to BPPC Migration
BPPB-based I /O packs
GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I
In a Mark VIe controller, the Auto-Reconfiguration feature
allows replacement of I/O packs without any manual
configuration. Auto-Reconfiguration is not available with
the Mark VIeS Safety controller. When
Auto-reconfiguration is used during the migration of Mark
VIe BPPB to BPPC-based I/O packs, the following items
are required:
ControlST V04.04 or later must be installed across the
Mark VIe system
The correct BPPC-based I/O pack firmware must be
installed on the HMI
Auto-Reconfiguration feature must be enabled on each
Mark VIe controller with associated I/O packs
Note There are three Mark VIe BPPB-BPPC migrations not
supported by Auto-Reconfiguration. The following modules
must be manually configured:
PPROH1A to PPROS1B
PPRAH1A to PPRAS1B
PCAAH1A to PCAAH1B