Power requirements for a typical large, four-cabinet turbine control containing controllers, I/O, and terminal boards are
displayed in the following table. The total cabinet current ratings must include the current supplied to external loads, such as
solenoids and ignition transformers as described in the notes below the table. Heat dissipation in a typical TMR turbine
control is about 1600 watts. However, power supply mains and heat dissipation requirements must be calculated for each
Mark VIe cabinet application based on the number and mix of controllers, I/O modules, IONet switches, power supplies, and
external loading.
Cabinet
Large,
125 V dc
four-cabinet
120 V ac
turbine control
240 V ac
1.
Add 0.5 A dc
continuous for each 125 V dc external solenoid powered.
2.
Add 6.0 A rms
for a continuously powered ignition transformer (2 maximum).
3.
Add 3.5 A rms
for a continuously powered ignition transformer (2 maximum).
4.
Add 2.0 A rms
continuous for each 120 V ac external solenoid powered (inrush 10 A).
Note
These are external and do not create cabinet heat load.
Installation Guidelines
Power Requirements for Control Cabinets
Voltage
± 10%
± 10%
± 10%
Public Information
Frequency
Current Requirements
N/A
N/A
15.0 A dc (Note 1)
50/60 Hz
±3 Hz
20.0 A rms (Notes 2, 4)
50/60 Hz
±3 Hz
10.0 A rms (Notes 3, 4)
GEH-6721_Vol_I_BP System Guide 133