From the ToolboxST application, perform a manual Download of the firmware.
Note If the Download is not successful, manually restart the I/O module and perform the Download again.
3. If an I/O module displays
Check the Component InfoView Log tab for errors. If there is a mismatch between the I/O module configured in the
ToolboxST application and the actual hardware, the I/O module configuration must be updated to match the hardware.
If there is still an issue with the download and the hardware configuration has been verified, restart the I/O module, wait
one minute, and perform the download again.
When the download has completed successfully, open the Download wizard and verify that all I/O modules are equal
(display green). Check the InfoView log and resolve any
8.9.3 Active Diagnostics
If the Warning symbol
I/O module has active diagnostic alarms
Firmware and/or application revisions in the I/O module do not match the ToolboxST configuration
➢ ➢ To clear active diagnostics
From the Component Editor Hardware tab, select the Diagnostics tab.
1.
2.
Select the diagnostic alarm with the red icon and press F1 to display the Help file.
Use the possible causes and solutions provided for the specific alarm number to correct the problem.
3.
192
GEH-6721_Vol_I_BP
during the download, complete the following:
displays on an I/O module:
GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I
Communication
Errors.
Public Information

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mark vies

Table of Contents