6.1.8

Electrical data

Voltage supply
Electrical safety
Protection rating
Power consumption
AC 110 to 240 V
AC/DC 20 to 30 V
Data backup
Data buffering
Clock
Electrical connection
Conductor cross section
Wire or strand without ferrule
Strand with ferrule
2 × strand with twin ferrule
with plastic collar
Stripping length
Conductor cross section
Wire or strand without ferrule
Strand with ferrule
Stripping length
Voltage supply influence
AC 110 to 240 V +10/-15 %, 48 to 63 Hz or
AC/DC 20 to 30 V, 48 to 63 Hz (not in conjunction with extra code 970)
According to DIN EN 61010-1
Overvoltage category II up to 300 V mains voltage, pollution degree 2
I with internal isolation from SELV
< 45 VA
< 30 VA
Internal flash memory
Battery (operating life > 7 years); additionally, storage capacitor for buffering
during battery change (buffer time approx. 6 minutes)
Battery-buffered real-time clock
On the back via push-in spring-cage terminals
At plug connector 4 and 5 (voltage supply and relay)
2
Min. 0.2 mm
, max. 2.5 mm
2
Min. 0.25 mm
, max. 2.5 mm
2
Min. 0.5 mm
, max. 1.5 mm
10 mm
At plug connector 6 to 15 (inputs and outputs)
2
Min. 0.14 mm
, max. 1.5 mm
Without plastic collar: min. 0.25 mm
With plastic collar: min. 0.25 mm
9 mm
< 0.1 % of the measuring range
2
2
2
(both strands with identical cross section)
2
2
, max. 1.5 mm
2
2
, max. 0.5 mm