6.1

Technical data

6.1.1

Analog inputs (options 1 and 2)

General information
Quantity
Connector number (back of
device)
Thermocouples
Description
Fe-CuNi
Fe-CuNi
Cu-CuNi
Cu-CuNi DIN
NiCr-Ni DIN
NiCr-CuNi
NiCrSi-NiSi
Pt10Rh-Pt
Pt13Rh-Pt
Pt30Rh-Pt6Rh
W5Re/W26Re
W3Re/W25Re
W5Re/W20Re
Chromel-Copel
Chromel-Alumel
Ambient temperature influ-
ence
Smallest measuring span
Measuring range start/end
Cold junction
Reference point accuracy
(internal)
Reference point tempera-
ture (external)
Sampling rate
Input filter
Galvanic isolation
Base measuring range
1
The accuracy value refers to the maximum measuring range. Small measuring ranges lead to reduced linearization
accuracy.
0, 3, or 6
7 to 9, 11 to 13
Typ
Standard
e
"L"
DIN 43710
"J"
IEC 60584-1
"U"
DIN 43710
"T"
IEC 60584-1
"K"
IEC 60584-1
"E"
IEC 60584-1
"N"
IEC 60584-1
"S"
IEC 60584-1
"R"
IEC 60584-1
"B"
IEC 60584-1
"C"
ASTM E230M-11
"D"
ASTM E1751M-09
"A1" GOST R 8.585-2001
"L"
GOST R 8.585-2001
GOST R 8.585-2001
≤ 100 ppm/K
Type L (Fe-CuNi), J, U, T, K, E, N, Chromel-Alumel: 100 K
Type S, R, B, C, D, A1, Chromel-Copel: 500 K
Freely programmable within the limits in steps of 0.1 K
Internal (Pt100) or external (constant)
± 1 K
-30 to +85 °C (adjustable)
3 or 6 channels: 125 ms
Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s
See "Galvanic isolation"
20 to 70 mV
ITS
Measuring range
ITPS-68
-200 to +900 °C
ITS-90
-210 to +1200 °C
ITPS-68
-200 to +600 °C
ITS-90
-270 to +400 °C
ITS-90
-270 to +1372 °C
ITS-90
-270 to +1000 °C
ITS-90
-270 to +1300 °C
ITS-90
-50 to 1768 °C
ITS-90
-50 to 1768 °C
ITS-90
0 to 1820 °C
ITS-90
0 to 2315 °C
ITS-90
0 to 2315 °C
ITS-90
0 to 2500 °C
ITS-90
-200 to +800 °C
ITS-90
-270 to1372 °C

6 Annex

1
Accuracy
≤ 0.25 %
≤ 0.25 % from -100 °C
≤ 0.25 % from -100 °C
≤ 0.25 % from -150 °C
≤ 0.25 % from -80 °C
≤ 0.25 % from -80 °C
≤ 0.25 % from -80 °C
≤ 0.25 % from 20 °C
≤ 0.25 % from 50 °C
≤ 0.25 % from 400 °C
≤ 0.25 % from 500 °C
≤ 0.25 % from 500 °C
≤ 0.25 % from 500 °C
≤ 0.25 % from -80 °C
≤ 0.25 % from -80 °C
69