Description; Brief Description; Block Diagram - JUMO LOGOSCREEN 600 Brief Instructions

Paperless recorder with touchscreen
Table of Contents

Advertisement

2.1

Brief description

The JUMO LOGOSCREEN 600 paperless recorder features a resistive touchscreen and an in-
tuitive, icon-based operation and visualization concept that makes it very easy to use.
There are different versions of the JUMO LOGOSCREEN 600 available for process data re-
cording. These range from the device version without measuring input in which up to 24 pro-
cess values are read (master) or received (slave) from external systems via Modbus, through
to a device version with six measuring inputs (universal analog inputs), two analog outputs, 12
digital inputs, and 12 individually switchable digital inputs/outputs. In the version with FDA-com-
pliant data recording all the requirements are met in accordance with 21 CFR Part 11.
The JUMO LOGOSCREEN 600 can display data using the default visualizations, such as
curve diagram (vertical or horizontal), bar graph, text image (numerical), or digital diagram. For
batch-related processes a special batch recording is available which allows the storage of ad-
ditional information. In addition, users can create up to six individual process screens with up
to 100 objects per process screen to fit their requirements using the setup program.
In addition to the setup program further powerful PC programs are available, e.g. for the eval-
uation of archived data and for the administration of access control.
2.2

Block diagram

Inputs/outputs
Option 1, option 2:
3 analog inputs,
6 digital inputs,
1 analog output
each
Option 3:
12 digital inputs/outputs,
incl. 1 high-speed counting input
(up to 12.5 kHz)
Inputs via interface
As standard:
24 external analog inputs and
24
external digital inputs and
14
external
texts (10 batch texts,
4 event texts)
Relay output
As standard:
1 relay (changeover contact)
Display/operation
Display
14,5 cm (5,7") TFT color screen
640 x 480 pixel,
65536 colors
Operation
Touchscreen (resistive)

2 Description

Voltage supply
AC 110 to 240 V +10/-15 %,
48 to 63 Hz
AC/DC 20 to 30 V, 48 to 63 Hz
Interfaces
As standard
:
1x Ethernet 10/100 MBit/s
1x USB host (flash drive)
1x USB device (setup)
1x RS232/RS485
(Modbus master/slave or
barcode scanner)
Measurem.-data memory
Internal memory:
1 GByte
(data transfer via interface
or USB flash drive)
Internal channels
6 math channels (optional)
6 logic channels (optional)
6 counters/integrators
1 high-speed counter
Software
Setup programm
PCC, PCA3000
PCS, PCAT
17

Hide quick links:

Advertisement

Table of Contents
loading