Digital Inputs/Outputs (Option 3); Analog Outputs (Options 1 And 2); Relay - JUMO LOGOSCREEN 600 Brief Instructions

Paperless recorder with touchscreen
Table of Contents

Advertisement

6.1.3

Digital inputs/outputs (option 3)

Quantity
Connector number (back of
device)
Input or output
Input
Level
Sampling rate
Potential-free contact
High-speed input
Function
Max. counting frequency
Mark-to-space ratio
Accuracy in flow measurement
Output
Output signal
Current
Auxiliary voltage
6.1.4

Analog outputs (options 1 and 2)

Quantity
Connector number (back of
device)
Voltage
Output signal
Load resistance
Current
Output signal
Load resistance
Accuracy
Ambient temperature influence
6.1.5

Relay

Quantity
Connector number (back of
device)
Relay (changeover contact)
Switching capacity
Contact life
0 or 12
14 and 15
Individually configurable as input or output
Logic level "0": < 3.5 V; logic level "1": > 10 V
125 ms (max. counting frequency: 8 Hz)
: < 1 kΩ; R
: > 50 kΩ (use of the auxiliary voltage 24 V)
R
ON
OFF
Input 1
Counts each positive edge of the input signal
12.5 k Hz
30 to 70 % (high-pulse ≥ 30 μs, low-pulse ≥ 30 μs)
0.5 % of measured value; ambient temperature influence: 50 ppm/K
DC 0/24 V +10/-15 %; galvanically isolated
Max. 40 mA per output, max. 100 mA on the whole
DC 24 V +10/-15 %, max. 100 mA (incl. current of digital outputs)
0, 1, or 2
6 and 10
DC 0 to 10 V
> 500 Ω
DC 0(4) to 20 mA
< 450 Ω
0.5 %
150 ppm/K
1
4
3 A at AC 230 V, resistive load
30,000 switching operations at rated load
6 Annex
73