2.2K Resistor Connection for Cut Off Check

You have to connect a 2.2K resistor between the input wire (e.g. Orange wire) and the GND
to apply the Cut Off Check feature. First, select whether or not to check the cutoff status of
each device from [F5 SETUP MENU] -> CUT OFF SET. Second, set the desired output that wil
l be generated in the event of a cutoff from [F5 SETUP MENU] -> CUT OFF ALARM.
4.3

Output Connection

Door Lock (Power Fail Safe) Connection (Door Relay)

1. Connect COM wire of Door Relay (Gray wire with Red stripe) to +12V.
2. Connect NC wire of Door Relay (Blue wire with White stripe) to (+) wire of Door Lock.
3. Connect GND wire to (-) wire of Door Lock.

Door Lock (Power Fail Secure) Connection (Door Relay)

1. Connect COM wire of Door Relay (Gray wire with Red stripe) to +12V.
2. Connect NO wire of Door Relay (White wire with Red stripe) to (+) wire of Door Lock
3. Connect GND wire to (-) wire of Door Lock.

Alarm Device Connection (Alarm Relay)

1. Connect COM wire of Alarm Relay (White wire) to +12V.
2. Connect NO wire of Alarm Relay (Purple wire) to (+) wire of Alarm device.
3. Connect GND port to (-) wire of Alarm device.