Site requirements

Inspect the site before you begin the installation. Verify that the site requirements have been met
for adequate environmental conditions, power and grounding availability, safety, and security
conditions. If you find discrepancies between the specifications necessary for proper installation of
equipment and the conditions on site, contact your project manager before proceeding with the
installation.
The Branch Gateway may be installed in a 19" rack, mounted on a wall, or placed on a sturdy
table. Installation instructions are provided in
ambient temperature should be in the range 32 to 104˚F (0 to 40˚C). The humidity should not be
higher than 90%.
Verifying temperatures and clearances
About this task
Verify that temperatures and clearances are within the recommended technical parameters.
Consult the table of Technical Specifications in the topic Technical Specifications.
Warning:
Verify that temperature and clearance ranges are within tolerable limits. The thermal sensors
may shut down equipment if it is subjected to conditions beyond the recommended limits.
Equipment can be damaged if these restrictions are not respected.
Verifying power outlets
About this task
Check that an adequate number of power outlets are available. Verify that the Branch Gateway
and the other equipment in the rack do not present a possible overcurrent or overload to the
customer's branch circuit and/or power distribution strip. Power requirements are listed in the topic
Power cord specifications.
Warning:
Do not overload the power circuit.
Verifying the grounds
About this task
Ensure that the installation site has access to approved grounds and that either a trained
technician or a licensed electrician will be verifying all grounds and installing the Supplementary
Ground Conductor (consult
Warning:
Installation in a Restricted Access Location and secure access are required in Finland,
Norway, and Sweden. The Branch Gateway relies on two ground connections: first, the mains
plugs for the power supplies are required to be connected to AC outlets that have earth
contacts; and second, the Supplementary Ground Conductor provided with the system
provides a non-removable ground even when the AC cords are disconnected. However,
July 2018
Installing the Branch Gateway
Attaching ground conductors
Deploying and Upgrading Avaya G430 Branch Gateway
Comments on this document? infodev@avaya.com
on page 22. The
on page 34).
Before you install
15