Setting by way of terminal strip forward/reverse; the sign of the set point values
have no effect on direction of rotation.
4
Setting by way of terminal strip run/stop (X2A.14) and forward/reverse (X2A.15);
negative values are set to zero
5
Setting by way of terminal strip run/stop (X2A.14) and forward/reverse (X2A.15);
the sign of the set point values have no effect on direction of rotation.
6
Set value dependent, positive value = clockwise rotation; negative value-
counterclockwise rotation; Status "Low speed" (LS) if no terminal For or Rev is
active
7
Set value dependent, positive value = clockwise rotation; negative value = counter
clockwise rotation clockwise rotation is indicated if set value is "0"
8/9
only application mode
CP.35 AN1 Set value selection
The set value input 1 (AN1) at the F5-GENERAL control can be triggered by various signal
levels. In order to correctly evaluate the signal, this parameter must be adapted to the
signal source. At the F5-BASIC control in A or B housing the signal source may not be
re-adjusted.
Value Set value signal
0
0...±10 V DC / Ri = 56 kΩ
1
0...+20 mA DC / Ri = 250 Ω
2
4...20 mA DC / Ri = 250 Ω
GB - 28