Environmental specifications
Primary Storage Shelf and Expansion Storage Shelf technical
Table A-2
specifications (continued)
Parameter
NetBackup 5330 Server with both a Primary
Storage Shelf and an Expansion Storage
Shelf connected
Total storage capacity: 229TB
Sound levels
The following table lists the requirements for the NetBackup 5330 Appliance and
the storage shelves.
Environmental specifications
Table A-3
Component
Operating temperature
Storage temperature
Transportation temperature
Temperature gradient
Operating humidity
Operating altitude
Storage altitude
Technical specifications, standards, and compliance information
Description
Watts: 2442 (typical)
Watts: 3194 (maximum)
Cooling BTU/hr: 8332 (typical)
Cooling BTU/hr: 10919 (maximum)
Sound power (standby operation): 6.5 bels
Sound power (normal operation): 6.8 bels
Sound pressure: 68 dB
Requirement
10°C to 35°C (41°F to 95°F)
-40°C to 70°C (-40°F to 158°F)
-40°C to 70°C (-40°F to 158°F)
10°C/h
10%RH to 85%RH
-30 meters to 3,000 meters
In altitudes from -60 meters to +1,800 meters,
the ambient temperature ranges from 5°C to
35°C. When the altitude ranges from 1,800
meters to 3,000 meters, the environment
temperature decreases by 0.6°C when the
altitude increases by 100 meters.
-30 meters to 3,000 meters
Environmental specifications