User Configuration - Definitions Of Access Levels - Eaton VoCALL 16 Installation And Operation Manual

Emergency voice communication system
Table of Contents

Advertisement

11.2 User Configuration - Definitions of Access levels

Post successful completion of system learn, next step is to define user settings
and details. In accordance with BS 5839-9:2011 standard, VoCALL 16 product range
provides following access levels for appropriate usage of the system.
1. Access level 1 – Members of public.
Outstations – Type A and Type B are readily available for usage by members of the
general public to initiate/ receive a call. No passwords/pin/key is required for use.
Functionality available - Start and end a call
2. Access level 2 – Authorized access for person who is trained by installer/
commissioner to operate the EVC system.
MX Panel features allows restricting its usage by an authorized person. Key lock
facility is provided to restrict usage of handset. 4-digit PIN is required to access the
system controls under – 'USER' profile. System can store up to 5 'uSEr' profiles.
Default functionality available for 'USER' profile:
A. Start and end a call – to give assistance to a member of the public.
B. Perform following operations on panel:
i.
View Event Log
ii.
View Fault Log
iii.
View Call Log
iv.
Change PIN
N
ote:
USER profile by default does not have permission to clear the faults on
the system.
Accepting fault by 'USER' would silence the buzzer for 8 hours. The buzzer
N
ote:
would sound again after 8 hours in case the fault is not corrected. In case of
detection of new fault on the system, buzzer would be active again.
N
ote:
Call functionality has higher priority over all other functions. During a call,
audible fault indications would be non-active for the duration of call and would
be reactivated once the call is completed.
3. Access level 3 – Authorized access for person who is trained to maintain the
EVC system. This access level allows basic fault finding and system maintenance.
4-digit PIN is required to access the system controls under - 'MANAGER' profile.
System can store up to 3 'mANAGEr' profiles.
Default functionality available for 'MANAGER' profile:
INStALLAtIoN ANd opErAtIoN mANuAL 25-16760-A January 2020 www.eaton.com
11. Commissioning
63