16. Logging facility

16.2 Fault logs

All Faults occurring on the system – MX, NX and connected Outstations are logged
on the respective panel. Date and time stamp is recorded for all faults. All fault
indications are indicated within 100s of their occurrence. If any fault occurs while a
call is in progress, audible indication for fault is suppressed. It will be restored within
100s of ending of call.
Active faults on any device installed on the network is indicated to MASTER panel.
Active faults log of MASTER panel records that the respective panel is in fault.
Fault log of the respective panel can then be accessed either remotely (via MASTER
panel) or locally. The fault log on all MX16 panels is accessible through the LCD
under "Fault Log" option.
Select a Panel 1-2
1 :01 - PANEL MX
2 :02 - PANEL XX
Logon to NX Panel: ID: 2
SW: X.XX SN: XXXXXX
Yes =
Figure 64. Local panel, accessed via mAStEr panel, log entry
Remote access of any panel (MX/NX) from MASTER puts the remote
N
ote:
panel in 'Engineering mode'. When in engineering mode the panel that is in
engineering mode cannot make, receive or transfer calls.
the following faults are detected by the panel:
Fault Type
Power Supply
In case of above faults, check the power connections – AC mains to pSu, pSu to
main board, pSu to battery, replacement of batteries. If the faults persist, call for
engineering support.
124
INStALLAtIoN ANd opErAtIoN mANuAL 25-16760-A January 2020 www.eaton.com
No =
shown on mAStEr panel.
Fault Name
PSU Not Found
AC PSU Fail
DC PSU Fail
Battery Charger
Battery Fault
Battery Resistance
Fault Log (1-15)
02/01/19 04:38.26
Battery Charger Fault
02/01/19 04:38.26
Battery Fault
02/01/19 04:19.04
Battery Charger Fault
Description
Panel is not able to communicate with PSU
AC power source is not available
DC power source is not available
Battery is not getting charged properly / battery is
not connected
Incorrect or broken battery is connected.
Battery resistance has increased over time beyond limit and
needs replacement.
1
2
3

Advertisement