GARDASOFT TR-HT2 Series User Manual page 66

Led controller
Table of Contents

Advertisement

gate input:
g =
f =
flags.
For example:
ZS1,3,2,0,2
Sets output channel 1 to pulse mode (Ptt), triggered by input 2, no
gate input, and flags = 2 (to invert the output).
parameter must be entered as a decimal number.
Set the output pulse timing
Use this command to set the output pulse delay and pulse width
timings:
ZTc,p,d
Where:
c =
output channel (1 to 2)
p = pulse width (time or encoder pulses)
d = delay time (time or encoder pulses)
The pulse width and delay times can either be set as a time period or
as a number of encoder pulses set in the mode parameter of the
ZS command.
For example:
ZT2,3ms,5K
Sets output channel 2 to provide a 3ms pulse after 5000 encoder
pulses.
Note:
Set the output mode with the ZS command before setting
the pulse timing.
Set the retrigger time
The retrigger time is the minimum time from when an output is
triggered to the next time it is triggered. The mode must be set
before the retrigger time.
ZRc,r
Where:
c =
output channel (1 to 4)
r =
retrigger time or number of pulses.
For example:
ZR2,10ms
TR-HT2xx LED Controller - User Manual
0 for none
1 to 4 for IP1 to IP4
5 to 6 for OP1 to OP2
66