Download Print this page

Wire Connection To Access Controller - IDTECK RFK101 Quick Installation Manual

Pin & proximity card reader
Hide thumbs Also See for RFK101:

Advertisement

4. Wire Connection to Access Controller

Access Controller
Main Power (+12V)
Power Ground (GND)
Wiegand Data 0
Wiegand Data1
Tamper Switch (INPUT)
Tamper Switch (COM)
Buzzer Control
LED Control (Red)
LED Control (Green)
LED Control (Yellow)
PC
Connection Parts
Main Power (+12V)
Wiegand Data Out
LED Control In
Buzzer Control In
RS-232-GND
Green with White stripe
White with Red stripe
Blue with White stripe
RS232 TX
RS232 GND
Connect DC+12V wire of Power to Red wire of RFK101 / IPK101.
Connect GND wire of Power to Black wire of RFK101 / IPK101.
Connect Green wire of RFK101 / IPK101 to Wiegand D0 input port of the
Controller.
Connect White wire of RFK101 / IPK101 to Wiegand D1 input port of the
Controller.
If you want to control LEDs, connect each LED Control wire (White with
red stripe, Yellow, Blue with White stripe wire) of RFK101 / IPK101 to GND
of controller. (In case of using a relay, connect NO to the LED Control wire
and COM to GND)
If you want to control the buzzer, connect Blue wire of RFK101 / IPK101 to
GND of controller.(In case of using a relay, connect the NO to the Blue
wire and COM to GND)
Connect to the COM port of the PC. (Connect pin #2 of the DB-9
connector to the purple wire; connect the black wire of the 6-pin connector
to pin #5 of the DB-9 connector).
Quick Installation Guide
Red
Black
Green
White
Gray
Blue
Yellow
Purple
Black
Connection Method
5

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Ipk101