Advertisement

AIR-TO-WATER HEAT PUMP

4.3 Electrical Data

Model
GRS-CQ6.0Pd/Na-K(I)
GRS-CQ8.0Pd/Na-K(I)
GRS-CQ10Pd/Na-K(I)
GRS-CQ12Pd/Na-K(I)
GRS-CQ14Pd/Na-K(I)
GRS-CQ16Pd/Na-K(I)
GRS-CQ6.0Pd/Na-K(O)
GRS-CQ8.0Pd/Na-K(O)
GRS-CQ10Pd/Na-K(O)
GRS-CQ12Pd/Na-K(O)
GRS-CQ14Pd/Na-K(O)
GRS-CQ16Pd/Na-K(O)
GRS-CQ12Pd/Na-M(I)
GRS-CQ14Pd/Na-M(I)
GRS-CQ16Pd/Na-M(I)
GRS-CQ12Pd/Na-M(O)
GRS-CQ14Pd/Na-M(O)
GRS-CQ16Pd/Na-M(O)
Note:
① Power cables are copper core cable and copper connectors must be used for power
cable connection.
② Leakage Switch is necessary for additional installation. If circuit breakers with
leakage protection are in use, action response time must be less than 0.1 second,
leakage circuit must be 30mA.
③ The above selected power cable diameters are determined based on assumption of
distance from the distribution cabinet to the unit less than 75m. If cables are laid out
in a distance of 75m to 150m, diameter of power cable must be increased to a
further grade;
④ Indoor/outdoor supply cable should be H05RN-F or above.
⑤ The power supply must be of rated voltage of the unit and special electrical line for
air-conditioning.
⑥ All electrical installation shall be carried out by professional technicians in
accordance with the local laws and regulations.
⑦ Ensure safe grounding and the grounding wire shall be connected with the special
grounding equipment of the building and must be installed by professional
technicians.
Leakage
Power Supply
V Ph Hz
220~240V-Ph-50Hz
380~415V-3Ph-50Hz
Minimum
Sectional Area of
Switch
Earth Wire
2
(A)
(mm
)
32
6
50
10
50
10
50
10
50
10
50
10
32
6
32
6
32
6
40
10
40
10
40
10
16
2.5
16
2.5
16
2.5
25
4
25
4
25
4
PRODUCT
Minimum
Sectional Area of
Power Supply
Wire
2
(mm
)
3×6
3×10
3×10
3×10
3×10
3×10
3×6
3×6
3×6
3×10
3×10
3×10
5×2.5
5×2.5
5×2.5
5×4.0
5×4.0
5×4.0
10

Hide quick links: