Required Accessories; Connecting S-Bus - Bosch Rexroth IndraControl S67 Series Application Description

Digital module 8 outputs
Hide thumbs Also See for Rexroth IndraControl S67 Series:
Table of Contents

Advertisement

32/69
Bosch Rexroth AG
Connecting Data and Supply Cables
6.2

Required Accessories

6.3

Connecting S-BUS

Rexroth IndraControl S67 Digital Module 8 Outputs – 2.0 A (4×M12)
The Bosch Rexroth accessory components listed below are required to con‐
nect data and supply cables. The corresponding ordering numbers are listed
in
chapter 13 "Accessories" on page
S-BUS terminator M12, degree of protection IP 67
S-BUS and supply cables ready-made at both ends, IP 67
Protective caps
The S-BUS is used for communication between a field bus coupler and the
connected IndraControl S67 components.
Prerequisite:
A Bosch Rexroth S-BUS cable ready-made at both ends is available. It
is required for an optimum signal transmission
The S-BUS terminator is available. It is necessary for communication
The following table outlines the assignment of the S-BUS connections:
Connection
OUT
IN
4
4
1
5
3
3
5
2
2
Tab. 6-1:
S-BUS: Pin assignment
To connect the S-BUS cable to the field bus coupler and to the modules, pro‐
ceed as follows:
1. Disconnect the power supply from those devices the S67-DO8-M12-2A
module is mounted to.
2. Connect the S-BUS cable (S1) to the OUT connections
field bus coupler and the IN connections
module. For example, if two modules are connected to the field bus cou‐
pler, connect the S-BUS cables (S1, S2) to the associated IN and OUT
connections as shown in the following figure.
3. Tighten the plugs and sockets using the knurled-head screws.
4. Attach the S-BUS terminator (T) to the last module and tighten the S-
BUS terminator (as shown in the figure).
DOK-CONTRL-S67DO8M122A-AP03-EN-P
59.
Contact
Description
IN
1
RD+
2
RD-
3
TD-
1
4
TD+
5
0 V DC
Connection
Shielded
thread
(1) of the S67-DO8-M12-2A
OUT
TD+
TD-
RD-
RD+
(3) of the

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth indracontrol s67-do8-m12-2aR911171792

Table of Contents