7 Short Floor

In some building the distance between two adjacent floors is not always the same. This happens in case of short floor. It
is possible to associate to the short floor a wished speed in order to calculate the best curve to approach the landing
floor.
The wished speed is set based on indication at paragraph 7.4. While the distance of the short floor is set based on
parameter that can be selected in the parameter group 11102 -11118 (see picture distance d1). When the car move in
the short floor a specific speed is communicated by the controller to the drive. The drive knowing speed and distance can
calculate the right curve to approach. For example to associate the speed of the short floor to the multispeed 2 the
following parameter must be set to the distance d1.
Menu
5.5.3
ADL300 - Fast installations and commissioning
Parameter
Description
11106
Distance multispeed 2
Default Value
0,0
Set to
0,0 – 10,0
Pag. 35 of 52