Bit 08, Jog
Bit 08='1': The output frequency is determined by 3-11 Jog
Speed [Hz].
Bit 09, Selection of ramp 1/2
Bit 09="0": Ramp 1 is active (3-41 Ramp 1 Ramp Up Time to
3-42 Ramp 1 Ramp Down Time).
Bit 09="1": Ramp 2 (3-51 Ramp 2 Ramp Up Time to
3-52 Ramp 2 Ramp Down Time) is active.
Bit 10, Data not valid/Data valid
Tell the frequency converter whether to use or ignore the
control word.
Bit 10='0': The control word is ignored. Bit 10='1': The
control word is used. This function is relevant because the
telegram always contains the control word, regardless of
the telegram type. Turn off the control word if not wanting
to use it when updating or reading parameters.
7
7
Bit 11, Relay 01
Bit 11="0": Relay not activated.
Bit 11="1": Relay 01 activated provided that Control word
bit 11=36 is chosen in 5-40 Function Relay.
Bit 12, Relay 02
Bit 12="0": Relay 02 is not activated. Bit 12="1": Relay 02 is
activated provided that Control word bit 12=37 is chosen in
5-40 Function Relay.
Bit 13, Selection of set-up
Use bit 13 to choose from the 2 menu set-ups according
to the table.
Set-up
Table 7.36
The function is only possible when Multi Set-Ups=9 is
selected in 0-10 Active Set-up.
Make a selection in 8-55 Set-up Select to define how Bit 13
gates with the corresponding function on the digital
inputs.
Bit 15 Reverse
Bit 15='0': No reversing.
Bit 15='1': Reversing. In the default setting, reversing is set
to digital in 8-54 Reversing Select. Bit 15 causes reversing
only when Ser. communication, Logic or Logic and is
selected.
92
Bit 13
1
2
MG18C402 - VLT
®
VLT
HVAC Basic Drive Design Guide
7.11.2 Status Word According to FC Profile
Slave-master
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
no.:
Illustration 7.14
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Table 7.37
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00='0': The frequency converter trips.
0
Bit 00='1': The frequency converter controls are ready but
1
the power component does not necessarily receive any
power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready
Bit 01='1': The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop
Bit 02='0': The frequency converter releases the motor.
Bit 02='1': The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03='0' : The frequency converter is not in fault mode.
Bit 03='1': The frequency converter trips. To re-establish
operation, press [Reset].
®
is a registered Danfoss trademark
(STW) (8-30 Protocol = FC profile)
STW
Output freq.
Bit=0
Bit=1
Control not ready
Control ready
Drive not ready
Drive ready
Coasting
Enable
No error
Trip
No error
Error (no trip)
Reserved
-
No error
Triplock
No warning
Warning
Speed ≠ reference
Speed=reference
Local operation
Bus control
Out of frequency limit
Frequency limit OK
No operation
In operation
Drive OK
Stopped, auto start
Voltage OK
Voltage exceeded
Torque OK
Torque exceeded
Timer OK
Timer exceeded