RS-485 Installation and Set...
STX
LGE
Illustration 7.5
Parameter block
The parameter block is used to transfer parameters
between master and slave. The data block is made up of
12 bytes (6 words) and also contains the process block.
STX
LGE
Illustration 7.6
7
7
Text block
The text block is used to read or write texts via the data
block.
STX
LGE
Illustration 7.7
7.4.7 The PKE Field
The PKE field contains two subfields: Parameter command
and response (AK) and Parameter number (PNU):
AK
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Illustration 7.8
Bits no. 12-15 transfer parameter commands from master
to slave and return processed slave responses to the
master.
80
VLT
ADR
PCD1
ADR
PKE
IND
ADR
PKE
IND
PKE
IND
PWE
high
PNU
MG18C402 - VLT
®
HVAC Basic Drive Design Guide
PWE
PWE
high
low
Ch1
Ch2
Chn
Parameter commands master ⇒ slave
Bit no.
15
14
0
0
0
0
0
0
PWE
low
0
0
1
1
1
1
1
1
Table 7.5
Response slave ⇒master
Bit no.
15
14
0
0
0
0
0
0
0
1
1
1
Table 7.6
®
is a registered Danfoss trademark
PCD2
PCD1
PCD2
PCD1
PCD2
Parameter command
13
12
0
0
No command
0
1
Read parameter value
1
0
Write parameter value in RAM (word)
1
1
Write parameter value in RAM (double
word)
0
1
Write parameter value in RAM and
EEprom (double word)
1
0
Write parameter value in RAM and
EEprom (word)
1
1
Read text
Response
13
12
0
0
No response
0
1
Parameter value transferred (word)
1
0
Parameter value transferred (double
word)
1
1
Command cannot be performed
1
1
text transferred
BCC
BCC
BCC