Specification
Maximum number of detectors per zone
Thresholds for zone conditions
• 0 - 2 mA
• 2 - 6 mA
• 6 - 110 mA
• 110 mA - Short circuit
Power Supply
Main Power supply
Standby Power supply
Maximum current available for system
devices (with fully charged battery)
Current consumption - mains failure
Outputs
Sounder Circuit 1
Sounder Circuit 2
Fault Relay, volt free changeover contacts*
Fire Relay, volt free changeover contacts*
*
Note: These functions may not be used to provide any "Options with requirements" as specified
in EN 54-2.
Auxiliary output
Cabling
Environment
Working temperature
Storage temperature
Humidity
10
Up to 20 conventional detectors and
unlimited number of manual call points.
Open circuit fault condition.
Normal condition.
Fire Alarm condition.
Short circuit condition.
230V AC ± 10%
0.315A fuse
1 x 12V / 7Ah
2A fuse
0.7 A
50 mA
24V / 0.315A
0.3A fuse
24V / 0.315A
0.3A fuse
3A @ 120V AC
3A @ 60V DC
3A @ 120V AC
3A @ 60V DC
24V DC 0.315A fuse
Maximum 2.5mm diameter
0 to 40°C
-20 to 60°C
0 to 95%