Backfeed Protection - CyberPower OL10000RT3UTF User Manual

Table of Contents

Advertisement

BACKFEED PROTECTION OPERATION
1. If the Bypass circuit is shorted and the UPS is running in Line Mode or Battery Mode, backfeed protection will be active and the external isolation device
(Magnetic Contactor) will open.
2. Save your data and perform a controlled shutdown.
3. Contact CyberPower for repair.
WITHOUT BACKFEED PROTECTION CONFIGURATION
1. Hardwire the input terminals as shown in the following diagram.
2. Do not remove the interconnection wires (Jumper1 / Jumper2) on "Backfeed Protection Connector".
Mains
L1 L2 PE
WITH BACKFEED PROTECTION CONFIGURATION
1. Customers should provide an external isolation device (Magnetic Contactor) which is upstream and outside the UPS and capable of supporting the UPS
input current.
2. Remove the interconnection wires (Jumper1 / Jumper2) on "Backfeed Protection Connector".
3. Hardwire the input terminals and "Backfeed Protection Connector" as shown in the following diagram.
4. The external isolation device must be installed in the Mains path.
Mains
L1 L2 PE
Copyright © 2011 CyberPower Systems, Inc.

BACKFEED PROTECTION

Jumper1
Jumper2
A1
L1
L1
MC
L2
L2
A2
2A Fuse
(Slow Blow)
UPS
I/P
L1
L1
L1
EMI
L2
L2
L2
PE
1
2
Backfeed
3
4
5
UPS
I/P
L1
L1
L1
EMI
L2
L2
L2
PE
1
2
Backfeed
3
4
5
8
IP-L1
IP-L2
PSDR
AC-L1
AC-L2
IP-L1
IP-L2
PSDR
AC-L1
AC-L2

Advertisement

Table of Contents
loading

Table of Contents