MAINTENANCE BYPASS MODULE
INSTALLATION CONT.

WITHOUT BACKFEED PROTECTION CONFIGURATION

1.
Hardwire the input terminals as shown in the following diagram.
2. Do not remove the interconnection wires (Jumper1 / Jumper2) on "Backfeed Protection Connector".

WITH BACKFEED PROTECTION CONFIGURATION

1.
Connect a user supplied external isolation device (Magnetic Contactor) upstream and outside the UPS
and capable of supporting the UPS input current.
2. Remove the interconnection wires (Jumper1 / Jumper2) on "Backfeed Protection Connector".
3. Hardwire the input terminals and "Backfeed Protection Connector" as shown in the following diagram.
4. The external isolation device must be installed in the Mains path.
Mains
L1 L2 PE
Jumper1
Jumper2
Mains
L1 L2 PE
A1
L1
L1
MC
L2
L2
A2
2A Fuse
(Slow Blow)
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.