NCB-EL Installation
Step 3. Route power wiring in conduit through the bottom of cabinet and connect the wiring to the
NOTE: Use only wire for power limited systems
or equivalent cabling per NEC 760.
Step 4. Connect the HSP-121's EQUIP side (output) to single, grounded electrical outlet that will
Step 5. Install the outlet into the single gang electrical box.
Step 6. Install the single gang electrical box's plate.
NOTE: Power-limited and non-power-limited circuits must remain separated in the cabinet
power-limited wiring must remain at least 0.25 inches from any non-power-limited circuit wiring
all non-power-limited wiring along bottom of cabinet
wiring must enter and exit the cabinet through different knockouts and/or conduits.
IFI Routers/Repeaters Installation & Operation Manual - P/N: 53388:Rev: A1 5/5/09
line side (input) of the HSP-121.
be mounted in the single gang electrical box.
Figure 5.4 Power Outlet Installation Diagram
.
Power limited wire runs use type FPLR, FPLP, FPL
.
All power-limited and non-power-limited circuit
NCB-EL Routers
.
All
.
Run
39