4Wrmb Installation; 1: Required Components; 2: Installation Overview; 3: 4Wrmb Power Requirements - Johnson Controls Intelligent Fire Integrator ROUTMB Installation & Operation Manual

For johnson control echelon networks
Table of Contents

Advertisement

4WRMB Installation

2.2 4WRMB Installation
2.2.1 Required Components
4WRMB motherboard.
SMX Echelon network transceivers (ordered separately - FTXC, or FOXC).
NOTE: The 4WRMB does not support DFXC transceivers.
A regulated, UL 1481 listed, power limited, battery backed, +24 VDC power supply (+24
VDC @ 0.050 A).
JNISCAB-1 enclosure (ordered separately).
2.2.2 Installation Overview
This is the recommended installation order for a 4WRMB:
1.
Secure SMX transceivers and wires on repeater before inserting repeater into JNISCAB-1.
2.
Install repeater in cabinet.
2.2.3 4WRMB Power Requirements
The 4WRMB requires +24 VDC @ 0.050 A nominal and battery backup in accordance with local
code requirements. It can be powered by any regulated, UL 1481 listed, power limited, battery
backed +24 VDC power source. Power connections are made via plug-in screw terminals.
IFI Routers/Repeaters Installation & Operation Manual - P/N: 53388:Rev: A1 5/5/09