Johnson Controls JC-RTR11002-0 Installation Manual
Johnson Controls JC-RTR11002-0 Installation Manual

Johnson Controls JC-RTR11002-0 Installation Manual

Bacnet router

Advertisement

Quick Links

Application
The BACnet
Router facilitates communication between
®
BACnet/IP and BACnet MS/TP networks to monitor and
control a wide variety of HVAC equipment, meters, fire
alarm panels, and lighting on the Building Automation
System (BAS).
Installation
Follow these guidelines when you install the BACnet
Router:
Transport the device in the original container to
minimize vibration and shock damage to the router.
Verify that all the parts shipped with the device are
present.
Do not drop the device or subject it to physical shock.
Important: Do not open the BACnet Router housing
for any reason. The device has no user-serviceable
parts inside. Tamper-evident labels on the device
caution installers, service technicians, building
owners, and our RMA inspectors from unauthorized
opening or tampering of the device.
Parts included
One JC-RTR11002-0 BACnet Router
One JC-RTR11002-0 BACnet Router Pack Sheet
Materials and special tools needed
A wall mounting requires three M4 (#8) fasteners
appropriate for the mounting surface.
A DIN rail mounting requires one 19.0 cm (7.5 in.)
or longer piece of 35 mm (1 1/8 in.) DIN rail and
appropriate hardware.
JC-RTR11002-0 BACnet Router Installation Guide
Device diagram
Figure 1: BACnet Router device diagram
Callout
Description
1
Reset button. See
2
Recovery button. See
3
Supply power adapter connection: 24 VDC
barrel jack. See
4
Supply power removable terminal block: gray
terminals, 24 VAC, Class 2. See
5
FC bus port: RJ-12 6-pin modular jack. The
RJ-12 jack is a future enhancement.
6
FC Bus removable terminal block for FC
BUS-1: blue terminal. See
blocks.
7
End-of-line (EOL) switch for FC BUS-1. See
Setting end-of-line
8
USB-1 and USB-2 ports are future
enhancements.
9
Micro-USB port is a future enhancement.
10
One Ethernet port, 100/10 Mbps, 8-pin RJ-45
connector. See
11
Multi-color LED status indicators. See
status
indicators.
LIT-12014229
Release 13.0
2023-10-04
Reset
button.
Recovery
button.
Power
supply.
Power
supply.
FC bus terminal
switches.
Ethernet
port.
LED
JC-RTR11002-0

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls JC-RTR11002-0

  • Page 1 Callout Description Reset button. See Reset button. • One JC-RTR11002-0 BACnet Router • One JC-RTR11002-0 BACnet Router Pack Sheet Recovery button. See Recovery button. Materials and special tools needed Supply power adapter connection: 24 VDC barrel jack. See Power supply.
  • Page 2: Wiring Overview

    USB connections. All terminal blocks are removable. place while you push up on the lower mounting This device can integrate to an MS/TP field controller (FC) clips to secure the device. trunk. The rules, guidelines, and wiring considerations for JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 3 JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 4 This can affect any of the terminal blocks. Torquing the terminal screws while the terminal blocks are attached to JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 5: Setup And Adjustment

    Setting end-of-line switches The network devices at each end of an FC bus segment must be set as network terminated devices. The device has one EOL switch for each of its FC bus connections that JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 6 Hardware tab of the remote field bus of the supervisory device. Click Command. From the Command list, select Activate Changes. From the Value list, select Update All Changes Pending Attributes and Restart Device. JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 7: Troubleshooting

    Point. Discovery is selected by default. Click DISCOVERY. When the discovery is complete, select the points that you want to add to the field device by clicking or tapping the check boxes. Click or tap NEXT. JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 8 FC BUS-1 Green Flashing 1 blink per second = data transmission with normal communication over FC BUS-1 Devices are defined on FC BUS-1, but none are communicating. Only the device is transmitting. No data transmission JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 9 Recovery button and release after 1 second. If this has no effect, the newer firmware version is active and behaves as described below. If this initiates the recovery sequence, the older version is active and exhibits older Recovery button behavior. JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 10: Technical Specifications

    Terminations FC devices with EOL switch in the ON position, one at each end of each FC Bus segment Technical specifications Table 4: JC-RTR11002-0 BACnet Router technical specification Specification Description Power requirement Dedicated nominal 24 VAC, Class 2 power supply (North America), SELV power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum) Alternate: Dedicated nominal 24 VDC, Class II power supply input;...
  • Page 11 Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada Compliant, ICES-003 Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive.
  • Page 12: North American Emissions Compliance

    Table 5: JC-RTR11002-0 BACnet Router Standard Control Panel Assembly technical specifications Specification Description Dimensions (height x width x depth) 20 in. x 16 in. x 6.50 in. (406 mm x 508 mm x 165 mm) Panel weight 45 lbs (20.4 kg)
  • Page 13: Contact Information

    GLENDALE, WI NO. 32 53209 NETHERLANDS MANCHESTER CHANGJIANG M40 2WL RD NEW UNITED DISTRICT KINGDOM WUXI JIANGSU PROVINCE 214028 CHINA Contact information Contact your local Johnson Controls representative: www.johnsoncontrols.com/locations Contact Johnson Controls: www.johnsoncontrols.com/ contact-us   JC-RTR11002-0 BACnet Router Installation Guide...
  • Page 14 © 2023 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. www.johnsoncontrols.com...

Table of Contents