MS-ZFR1812-x
Application
Use the ZFR1812 Wireless Field Bus Router only to
provide an input to equipment under normal
operating conditions. Where failure or malfunction of
the ZFR1812 Router could lead to personal injury or
property damage to the controlled equipment or
other property, additional precautions must be
designed into the control system. Incorporate and
maintain other devices, such as supervisory or
alarm systems or safety or limit controls, intended to
warn of or protect against failure or malfunction of
the ZFR1812 Router.
IMPORTANT: The ZFR1800 Series Wireless Field
Bus System is not designed or intended for use in
mission-critical or life/safety applications.
A ZFR1812 Wireless Field Bus Router is used with
Advanced Application Field Equipment Controllers
(FACs), Field Equipment Controllers (FECs), Input/
Output Modules (IOMs), and Variable Air Volume
Modular Assembly (VMA) Series field controllers.
The ZFR1812 Router provides a wireless interface
between:
a field controller and the supervisory controller (by
means of a ZFR1810 Coordinator)
a field controller and associated WRZ Series
Wireless Room Sensors
Additionally, the ZFR1812 Wireless Field Bus Router
can be used as a repeater in WRZ-7860-0 One-to-One
Wireless Room Temperature Sensing System. For
more information, refer to the WRZ Series One-to-One
Wireless Room Sensing System Technical Bulletin
(LIT-12011641).
Up to nine WRZ Series Sensors can be associated
with a single field controller. In multi-sensor
applications, the ZFR1812 Router passes all the
sensor data to an FAC, FEC, IOM, or VMA controller,
which can be configured to either average the sensors'
input or select the highest or lowest sensed condition
for control of the target zone.
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
A ZFR1812 Router is powered directly from the
connected field controller's 15 VDC output.
The ZFR812 Router is also included in the Repeater
Accessory Kits, MS-ZFRRPTK-H1 or MS-ZFRRPTK-
H2. These kits include a 24 VAC to 15 VDC converter
power supply for stand-alone operation. As a repeater,
the ZFR1812 extends the range and strengthens the
wireless mesh network.
Refer to the ZFR1800 Series Wireless Field Bus
System Technical Bulletin (LIT-12011295) or the
ZFR1800 Series Wireless Field Bus System Quick
Reference Guide (LIT-12011630) for information on
commissioning and configuring a ZFR1800 Series
Wireless Field Bus System for operation.
North American Emissions Compliance
United States
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference,
and
2. This device must accept any interference
received, including interference that may cause
undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by
the party responsible for compliance could void the
user's authority to operate the equipment.
Canada
Industry Canada Statement
The term IC before the certification/registration
number only signifies that the Industry Canada
technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est
conforme aux spécifications techniques d'Industry
Canada.
1
Part No. 24-10325-45, Rev. A
Issued April 2016

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls ZFR1812

  • Page 1: Installation Instructions

    Application A ZFR1812 Router is powered directly from the connected field controller’s 15 VDC output. Use the ZFR1812 Wireless Field Bus Router only to The ZFR812 Router is also included in the Repeater provide an input to equipment under normal Accessory Kits, MS-ZFRRPTK-H1 or MS-ZFRRPTK- operating conditions.
  • Page 2: Installation

    The ZFR1812 can be mounted directly to drywall with drywall anchors. Both the standalone and repeater kit Follow these guidelines when installing a versions of the ZFR1812 include a 10 foot long RJ12 ZFR1812 Router: cable hardwired to the device. The Repeater Kit •...
  • Page 3 A template (Figure 11) is provided at the end of Note: Any inline adapter used to extend the this document to help you place the mounting connection of the ZFR1812 to a controller or power holes. must be a straight through adapter instead of b.
  • Page 4 This connector (3) is then used to connect to the 10ft RJ12 cable which is attached to the ZFR1812. 8. Mount the wall plate with ZFR1812 in the selected location using standard box screws. Be sure to leave enough slack in the cable so you can still pull...
  • Page 5 The preferred orientation for the ZFR1812 Router is in Wireless Signal Transmission Considerations a horizontal orientation with the green LED at the top. If Line-of-sight transmission ranges between a you feel that you are not able to get proper signal...
  • Page 6 IOMs cannot be used in wireless mode to extend the IO of a field controller. You must always hardwire IOMs to their host field controller. Do not connect any device to the SA Bus/FC Bus terminal block when using the IOM with a ZFR1812. For further information on how to set up a field •...
  • Page 7: Setup And Adjustments

    Power down the ZFR1812 and toggle the switches (all off, then all on) and then set the switches to the desired PAN. Restore power to the ZFR1812 and see that it joins the correct network. •...
  • Page 8: Troubleshooting

    Strength LED flashes to indicate the strength of the signal received from neighboring devices. See Table 3. Note: The Signal Strength LEDs on all the ZFR1812 routers in a network extinguish after approximately 2 hours of normal operation, making the ZFR1812 less distracting when installed in an open area.
  • Page 9 The Signal Strength LEDs on all the ZFR1812 Routers in a network extinguish after approximately 2 hours of normal operation, making the ZFR1812 less distracting when installed in an open area. To re-enable the ZFR1812 LEDs for troubleshooting purposes, perform a scan using the ZCT or push the Network Optimize/Reform Push Button on the ZFR1810 Coordinator.
  • Page 10: Repair Information

    ZFR router is better facilitated using a ½ Inch conduit EMT connector. MS-ZFRRPTK-H1 ZFR1812-0 wireless router repeater kit. Includes ZFR1812 router, 24 VAC to 15 VDC power supply, RJ-12 cable for power extension, and mounting hardware.
  • Page 11: Technical Specifications

    MS-ZFR1812-0: Field Equipment, Wireless Interface, Surface Mount, includes hardwired 10 foot RJ-12 cable. MS-ZFRRPTK-H1: ZFR1812-0 wireless router repeater kit. Includes ZFR1812 router, 24 VAC to 15 VDC power supply, RJ-12 cable for power extension, and mounting hardware. MS-ZFRRPTK-H2: ZFR1812-0 wireless router repeater kit. Includes ZFR1812 router, 24 VAC to 15 VDC power supply, RJ-12 cable for power extension, mounting hardware, and mounting plate.
  • Page 12 The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
  • Page 13 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc. ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions Published in U.S.A.