5. PARAMETER LIST

Display
* See page 44~46 for lock level.
* E.U.: Engineering Units
* D.E.U. : Deviation engineering Units
ogy Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE |
Lock
Name
level
Lock level
LOCK
0
Remote set
CAS
3
value
Control output 1
OUT1
output value
3
Control output 2
OUT2
output value
3
Control
MOD
mode
2
Autotuning
AT
1
command
Sub-Set point
D-SV
2
Ramp/soak
STAT
1
present point
Ramp/soak
TIME
1
remaining-
operation
time
Description
Parameter locking
(setting range: 0 ~ 3)
Displays the set value (SV) by
remote input.
(Displayed range: 0 to 100% FS E.U.)
Displays the output value of Copntrol
Output 1.
(display range: —3.0 ~ 103.0%)
Displays the output value of Copntrol
Output 2.
(display range: —3.0 ~ 103.0%)
Setting
Mode
Auto
Manual
Remote
Setting
Autotuning
Stop
Normal autotuning
Low-PV type autotuning
2-setting function sub-set point
(setting range: 0 ~ 100%FS E.U.)
Ramp/soak proceeding status is
displayed with a symbol. No setting
(display: OFF/1-RP/1-SK/2-RP/2-
SK/3-RP/3-SK/4-RP/4-SK/END)
The ramp/soak proceeding status is
displayed with the time for remaining
operation. When the time for
remaining operation exceeds 100
hours, the hours display of "xxxh" is
made. When the time is under 100
hours, the hour/min display of
"xx.xx" is made. No setting.
91
Initial
value
Remarks
during
shipment
2
Not displayed when
the remote SV
function is disabled.
No setting
No setting
Not displayed
unless control
output 2 is provided.
not
displayed when the
remote SV function
is disabled.
0%FS
Not displayed
E.U.
unless the 2-setting
function is provided.
Not displayed
unless the
ramp/soak function
is provided.