Output setting in input abnormal

Input abnormal-time output
In the event of an input PV error (e.g. thermocouple burn-out, sensor
disconnection or short-circuit, over-input, under-input etc.), or after the
ramp soak function (option) program ends, the value specified in
advance as the parameter
value.
Setting procedure
Supplement:
1. Set the parameter
be continued after the ramp soak function (option) program
terminates, with the set value prior to the program termination.
NOTES:
1. The parameter "
both cases of abnormal input and program end. In other words, the
same operation will be made after an input error and after the
program ends.
ogy Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE |
(input abnormal-time output selection code)
Code No. Control output 1
0
Going on control
1
2
3
4
is out put as the manipulated
Set the code number (0 ~ 4) by
referencing the following table.
Control output 2
Going on control
-3%
-3%
103%
103%
-3%
103%
-3%
103%
to "0" when the control is desired to
" specifies only one type of output for
76
Parameter to be used